-40%

6ES7 153-2BA70-0XB0 SIEMENS interface DP/PA-Link IM153-2 HF 6ES71532BA700XB0

$ 258.71

Availability: 100 in stock

Description

SIEMENS interface DP/PA-Link IM153-2 HF for extended temperature range
SIMATIC DP, interface DP/PA-Link and ET200M IM153-2 HF for extended temperature range for max. 12 S7-300 modules with redundancy capability. Timestamping suitable for isochronous mode. Up to 12 modules can be used
Slave Initiative for Drive ES and Switch ES
Expanded quantity structure for HART auxiliary variables
Operation of the 64-channel modules
32 signals / slot
Product type designation
IM 153-2 HF
Firmware version
V6.0.0
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Mains buffering
● Mains/voltage failure stored energy time
5 ms
Input current
Current consumption, max.
650 mA
Inrush current, typ.
3 A
I²t
0.1 A²·s
Output current
for backplane bus (5 V DC), max.
1.5 A
Power loss
Power loss, typ.
5.5 W
Address area
Addressing volume
● Inputs
244 byte
● Outputs
244 byte
Hardware configuration
Number of modules per DP slave interface, max.
12
Time stamping
Accuracy
1 ms; 1 ms at up to 8 modules; 10 ms at up to 12 modules
Number of message buffers
15
Messages per message buffer
20
Number of stampable digital inputs, max.
128; Max. 128 signals/station; max. 32 signals/slot
Time format
RFC 1119
Time resolution
0.466 ns
Time interval for transmitting the message buffer if a message is present
1 000 ms
Time stamp on signal change
rising / falling edge as signal entering or exiting
Interfaces
Transmission rate, max.
12 Mbit/s
1. Interface
automatic detection of transmission rate
Yes
Interface types
● Output current of the interface, max.
70 mA
● Design of the connection
9-pin sub D socket
PROFIBUS DP slave
● GSD file
SI05801E.GSG
● automatic baud rate search
Yes
Protocols
Bus protocol/transmission protocol
PROFIBUS DP to EN 50170
PROFIBUS DP
Services
— SYNC capability
Yes
— FREEZE capability
Yes
— Direct data exchange (slave-to-slave communication)
Yes; as publisher with all IO, as subscriber with F-IO only
Potential separation
Potential separation exists
Yes
Isolation
Isolation tested with
Isolation voltage 500 V
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-25 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
-25 °C
● vertical installation, max.
40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
3 000 m
Configuration
Configuration software
● STEP 7
Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file
Dimensions
Width
40 mm
Height
125 mm
Depth
117 mm
Weights
Weight, approx.
360 g